Every circuit breaker temperature rise test is run at 40 °C ambient, and almost every project this equipment is sold into is hotter than that. The nameplate current that a buyer compares across three quotations is only valid at the ambient the standard assumes; above it, the same hardware carries less. That gap is where a 3,150 A breaker ends up running at 2,900 A in a Gulf substation, where a joint that passed the factory test reaches 130 °C in service, and where a two-year-old unit starts showing tarnished silver on a terminal block that was bright when it left the works.
This article works through what the temperature rise test actually measures, what the IEC 62271-1 limits are for each part of the current path, and how to convert those limits into a derating factor for a site that spends five months a year above 45 °C. It also explains why a “1.1 times rated current continuous” requirement — common in Middle East and Southeast Asian specifications — cannot be met by simply overloading a standard frame, and what to ask for instead. If you are comparing high-voltage SF6 circuit breakers for a hot-climate project, the arithmetic below is the part of the datasheet that usually gets skipped.
What the temperature rise test actually measures
The test is simple in principle and unforgiving in practice. Rated normal current is passed through the main circuit, in still air, until temperatures stabilise, and the rise of each measured point above ambient is compared with the limit for that part. Stabilisation is normally taken as successive hourly readings differing by no more than 1 K. The ambient itself is measured with several thermocouples on a dummy of similar size, positioned around the test object, so that the local heating of the test bay does not get attributed to the equipment.
Three details decide whether the result means anything. The first is the absence of draught: a fan in the test hall, or an open door, changes the convective coefficient and can make a marginal design look comfortable. The second is the placement of the thermocouples, because the hot spot is almost never where the designer expects it — in practice it is usually the bolted connection between the busbar and the breaker terminal, not the contact inside the interrupter. The third is that main circuit resistance should be measured before and after the test: a resistance that climbs during the run tells you the joints are degrading under their own heat, which is a different and more serious finding than a single point reading high.
The temperature rise test belongs to the type-test family that also covers dielectric and short-circuit duties, described in the guide to SF6 circuit breaker type testing. What makes it different from the others is that it is the only one whose result is routinely invalidated by the installation rather than by the design.
The limits, part by part
IEC 62271-1 does not give a single permissible temperature rise. It gives a table of limits by material and by function, and the lowest applicable limit governs the design of the whole current path. The values below are the ones that matter for an outdoor SF6 breaker; they are from the 2017 edition, and editions differ, so the type test report is always the authority.
| Part of the current path | Material and medium | Max temperature | Max rise at 40 °C |
|---|---|---|---|
| Contacts | Bare copper or silver / nickel coated, in SF6 | 115 °C | 75 K |
| Contacts | Tin coated, in SF6 or air | 90 °C | 50 K |
| Bolted connections | Bare copper, in air | 90 °C | 50 K |
| Bolted connections | Bare copper, in SF6 | 105 °C | 65 K |
| Bolted connections | Silver or nickel coated | 115 °C | 75 K |
| Terminals for external conductors | Bare | 100 °C | 60 K |
| Terminals for external conductors | Silver or nickel coated | 115 °C | 75 K |
| Terminals for external conductors | Tin coated | 105 °C | 65 K |
| Accessible surfaces | Coated metal, touched in normal operation | 70 °C | 30 K |
| Accessible surfaces | Not normally touched | 80 °C | 40 K |
Two rows deserve attention. The 30 K limit on a surface that an operator touches in normal operation is a safety limit, not an equipment limit, and it is the reason enclosure surfaces are often designed to run cooler than the conductors inside them. The 50 K limit on tin-coated contacts is the one that quietly governs a surprising number of designs: tin is cheap, it plates well and it is used widely on secondary and auxiliary circuits, but a tin-plated joint has 25 K less budget than a silver-plated one. On a hot site, that difference is the whole margin.

Why 40 °C is baked into every rating
The rated normal current of a breaker is defined for an ambient air temperature not exceeding 40 °C, with the further condition that the average over any 24-hour period does not exceed 35 °C. That second clause is the one buyers forget, and it is more protective than it looks: a site that peaks at 47 °C for six hours and sits at 33 °C overnight has a 24-hour average that passes, while a site that holds 42 °C around the clock does not, even though its peak is lower.
The lower end of the ambient range is defined too — typically minus 5 °C for indoor equipment and minus 25 °C for outdoor, with minus 40 °C available by agreement. Cold is a different problem, handled through gas density and heating, and is covered in the article on cold-climate and high-altitude operation.
The reason 40 °C sits in the middle of the standard rather than at the top is historical: the limits were set so that a well-designed joint reaches its material limit at the same ambient that a human can still work in. Everything above that is a negotiated derating, and the negotiation is what the rest of this article is about.
The derating arithmetic
The temperature rise of a conductor carrying current is, to a good approximation, proportional to the square of the current. That single relationship is enough to build a derating table, because it means the permissible rise at a higher ambient can be converted into a permissible current directly.
Take a current path whose governing limit is 75 K at 40 °C. At 50 °C ambient the same absolute limit of 115 °C leaves only 65 K of rise available, and the permissible current falls by the square root of the ratio: √(65/75) = 0.93. At 60 °C it falls to √(55/75) = 0.86. If the governing limit is a tin-plated joint at 50 K, the fall is steeper, because the absolute ceiling is lower and the rise budget shrinks faster.
| Site ambient | Factor, 75 K limit | Factor, 50 K limit | What it means on a 3,150 A frame |
|---|---|---|---|
| 40 °C | 1.000 | 1.000 | 3,150 A |
| 45 °C | 0.966 | 0.949 | 3,043 A |
| 50 °C | 0.931 | 0.894 | 2,933 A |
| 55 °C | 0.894 | 0.837 | 2,816 A |
| 60 °C | 0.857 | 0.775 | 2,700 A |
The square-root law is a design tool, not a standard. It assumes that convection and radiation scale the same way, which is not exactly true, and it ignores the fact that the internal gas temperature of an SF6 interrupter rises with ambient pressure in a way that changes the heat transfer. Manufacturers publish measured derating curves from the temperature rise test for exactly this reason. The value of the calculation is that it tells you what order of magnitude to expect, so that a supplier quoting “no derating required up to 55 °C” is immediately recognisable as either unusually well designed or unusually casual.

The 1.1 times continuous trap
Many hot-climate specifications require the breaker to carry 1.1 times its rated current continuously. The intention is sensible — load growth, plus a margin for the day the ambient is worse than the design case — but the arithmetic behind the requirement is usually not followed through, and it produces a contradiction.
At 1.1 times rated current, the losses in the current path rise by 1.21, because they go with the square. A path designed to sit exactly at 75 K at rated current will therefore sit at about 91 K at 1.1 times, which puts it at 131 °C absolute in a 40 °C ambient — sixteen degrees above the 115 °C ceiling, before any ambient correction at all. In other words, a standard frame cannot meet a 1.1 times continuous requirement at 40 °C, let alone at 50 °C.
What the requirement actually asks for is a frame with about 21 percent more current capacity than the nameplate suggests, so that 1.1 times the declared current is still below the thermal limit. That is normally delivered by moving one frame size up, by increasing conductor cross-section, or by improving the cooling path — not by declaring a higher current on the same hardware. A quotation that answers “1.1 times continuous” without changing the frame is answering a different question, and the evidence will not be in the temperature rise report.
This is the point at which the thermal budget meets the short-circuit budget. A larger frame chosen for continuous current also changes the short-time and peak withstand capability, and the two are usually quoted together, so the frame change has to be checked against both duties rather than just the thermal one.
Where the heat actually comes from
Designers think about contacts, but field failures concentrate at joints. A silver-plated contact inside a sealed interrupter is protected from the atmosphere, operates in a controlled gas and is inspected at every service. A bolted aluminium-to-copper joint on an outdoor terminal is exposed to humidity, salt and thermal cycling, and its resistance creeps upward over years through oxidation and loss of bolt preload.
The practical consequence is that the temperature rise measured in the factory is a best case. It is measured with new plating, correct torque and clean surfaces. In service, the same joint can be several kelvin worse after three years, and that drift consumes derating margin that was never accounted for. Two habits address it: specify silver or nickel plating rather than tin on the main current path, and trend the main circuit resistance at each service interval rather than waiting for a thermal image to show a problem. The maintenance routine that covers this is described in the guide to SF6 circuit breaker maintenance.
Solar gain, enclosures and the difference between shade air and room air
The 40 °C ambient in the standard is shade air temperature. A live-tank breaker standing in direct sun in a Gulf yard is not at shade air temperature: the tank surface absorbs solar radiation and can run well above it, and the gas inside follows the tank. Measured tank surface temperatures 10 to 20 K above shade air are normal on a still afternoon, which is why manufacturers of equipment for that market offer solar-rated designs, white or light-grey finishes, and in some cases a lower declared current for unshaded installation.
Indoor equipment has its own version of the problem. A metal-enclosed switchgear room with blocked louvers, failed extraction or a roof that acts as a heat collector can sit 10 K above outdoor shade air, and the equipment inside sees that temperature as its ambient. When a project specifies “indoor, ambient 40 °C” but the room is ventilated only by two louvered doors, the real design case is closer to 50 °C. The enclosure classification matters here as much as the breaker rating, and the selection logic that ties the two together is set out in the guide to selecting an SF6 circuit breaker.
What sustained overtemperature actually does
Nothing dramatic happens on the first hot day. The failure mode is cumulative, and it runs on three parallel tracks.
The first is insulation ageing. The classic rule of thumb for electrical insulation is that life halves for every 8 to 10 K of sustained excess temperature. Applied to a joint running 15 K above its limit, that is roughly a factor of three reduction in service life — which converts a twenty-year asset into a seven-year one without any single event to point at.
The second is contact and joint degradation. Silver plating tarnishes faster above about 100 °C, particularly where sulphur compounds are present, and the tarnish layer raises resistance, which raises temperature, which accelerates the tarnish. Tin plating forms intermetallic compounds with copper above roughly 90 °C, and those compounds are brittle and higher in resistance than either metal. Both are runaway mechanisms once started, and both are invisible until a thermal survey or a resistance measurement finds them.
The third is gas pressure. An SF6 breaker is filled to a density that is set at 20 °C, and the pressure inside rises with temperature. A sealed design must accommodate the maximum pressure reached at the highest ambient, and a design that was qualified only to 40 °C may operate its relief device or stress its seals on a 55 °C afternoon. The density relay will not report a fault, because density is unchanged — the pressure rise is expected, and it is the mechanical containment that is being tested.
Specifying for a hot site
The fix is in the request for quotation, not in the negotiation after the fact. Six items, if they are stated, remove almost all of the ambiguity.
| Item to state | Why it changes the answer |
|---|---|
| Maximum shade air temperature and 24-hour average | Sets the derating factor; the average is a separate criterion from the peak |
| Solar exposure: shaded, partial or full sun | Moves the effective ambient by 10 to 20 K on a live-tank unit |
| Indoor or outdoor, and enclosure type | Room temperature and internal air movement change the convective path |
| Site altitude | Thinner air reduces convective cooling; above 1,000 m the standard requires agreement |
| Continuous overload requirement, if any | 1.1 times means a frame one size up, not a footnote |
| Temperature rise test report and derating curve | The only evidence that the declared current is valid at your ambient |
With those six answers, the comparison between suppliers becomes a comparison of evidence rather than of nameplate numbers. A 3,150 A frame that publishes a derating curve down to 0.93 at 50 °C is a better answer than a 4,000 A frame that publishes nothing, because the first has told you what it will do on your site and the second has told you what it did in a laboratory at 40 °C. The 3,150 A rated current frame and the 4,000 A porcelain column unit sit at different points on that curve, and the right choice depends on the site data rather than on which number is larger.
Where the ambient is genuinely extreme, the answer is sometimes a different frame rather than a derated one. A 4,000 A split-type unit at 252 kV has more conductor mass and more surface area than a 3,150 A frame, so its rise at the same current is lower and its derating curve is flatter. Paying for the larger frame is often cheaper than paying for the load restrictions that a derated frame imposes for the next twenty years.
Conclusion
Temperature rise is the least glamorous rating on a breaker datasheet and the one most likely to be wrong for your site. A circuit breaker temperature rise test is run once, in a still laboratory at 40 °C, and the number it produces is then applied to a yard that may be fifteen degrees hotter and in full sun. The nameplate value is valid at 40 °C shade air with a 35 °C daily average; everything else is a calculation, and the calculation is a budget of kelvin that gets spent by ambient, by solar gain, by altitude and by the slow degradation of joints. Convert the budget into a current factor before comparing quotations, treat a 1.1 times continuous requirement as a frame size rather than a tolerance, and ask for the derating curve with the offer. Those three habits will prevent most of the thermal problems that show up five years into a hot-climate project.
If you have the site ambient, the solar exposure and the continuous current requirement, the SF6 circuit breaker guides cover the rest of the selection chain. Send the four numbers and we will confirm which frame holds the rating at your temperature instead of at the standard’s.
FAQ
What is the permissible temperature rise for a circuit breaker?
It depends on the part. Under IEC 62271-1:2017, silver or nickel coated contacts and bolted connections in SF6 are limited to 115 °C absolute, which is a 75 K rise at 40 °C ambient; tin-coated contacts to 90 °C, a 50 K rise; bare copper bolted connections in air to 90 °C; and surfaces touched in normal operation to 70 °C, a 30 K rise.
How much current can a breaker carry at 50 °C ambient?
Roughly 93 percent of its rated current if the governing limit is 75 K, and about 89 percent if the limiting part is a tin-plated joint at 50 K. Both figures come from the square-root relationship between current and temperature rise. The measured derating curve in the type test report is the authority and usually differs by a few percent.
Why is the temperature rise test always run at 40 °C ambient?
Because 40 °C, with a 24-hour average of 35 °C, is the ambient the standard assumes when it defines rated normal current. The test measures the rise above ambient rather than absolute temperature, so a result obtained at 40 °C can be applied to other ambients by adjusting the allowable rise — provided the limit for the governing part is known.
Does a 1.1 times continuous current requirement mean I need a bigger breaker?
Usually yes. Losses rise with the square of current, so 1.1 times current produces 1.21 times the loss and about 21 percent more temperature rise. A standard frame designed to sit at its limit at rated current would exceed the absolute temperature ceiling, so meeting the requirement means selecting a frame with roughly 20 percent more capacity.
Does altitude affect the current rating as well as the insulation level?
It does. Thinner air reduces convective cooling, so the same losses produce a higher rise. IEC 62271-1 requires the current rating above 1,000 m to be agreed between purchaser and manufacturer; the effect is smaller than the dielectric correction but it is not zero, and on a hot site the two corrections compound.