Above about 245 kV a single interrupter stops being the economical answer. The gap needed to hold off the recovery voltage becomes so long that the mechanism, the gas volume and the energy needed to drive the arc all grow faster than the voltage does. So the industry does what it does everywhere else in EHV: it puts two, or four, interrupting gaps in series on the same pole. The moment you do that, a new problem appears. Series gaps do not share voltage in proportion to their number, and a grading capacitor circuit breaker design — a breaker with capacitors fitted across each break — exists because the natural voltage distribution is badly unequal.

This article works through the two passive components that make multi-break EHV breakers viable: the grading capacitor that fixes voltage sharing and transient recovery voltage, and the closing resistor that fixes the surge produced when the breaker energises a line. Both are small, both are cheap relative to the breaker, and both are the components that fail first when they are specified carelessly.

Why Series Breaks Do Not Share Voltage

A breaker with two breaks per pole does not put half the voltage on each break. What actually sets the division is a capacitive divider made of three things:

  • The interrupter’s own gap capacitance with the contacts open — small, in the tens of picofarads, and dependent on the contact position.
  • The capacitance from each break to earth — the support column, the tank wall, the surrounding structure. For an outdoor live-tank breaker this is larger than for a dead-tank or GIS design, because the column is exposed to a wide earth plane.
  • The grading capacitor, if one is fitted, in parallel with each break.

Consider a two-break pole with one terminal energised and the other at earth. The break nearest the energised terminal sees the other break’s capacitance plus the capacitance to earth in parallel, and the break nearest earth sees only the other break’s capacitance. Since the impedance of a capacitor falls as its value rises, the break with less effective capacitance in parallel takes more voltage. In the worst case — no grading capacitor at all, and a substantial capacitance to earth — the line-side break can take the overwhelming majority of the recovery voltage.

The published finite-element studies make the effect concrete. A 363 kV six-break vacuum breaker analysed without grading capacitors showed the first break carrying about 86 percent of the applied voltage, with a peak field of 18.9 kV/mm at that gap. With grading capacitors fitted, the same structure shared the voltage acceptably. The geometry and the numbers differ in an SF6 breaker, but the mechanism does not: the break nearest the live terminal is the one that gets hurt.

The consequence is not a small derating. A gap that is asked to hold 60 or 80 percent of the pole voltage instead of 50 percent will restrike at a lower system voltage than the type test promised, and the breaker’s rated breaking capacity becomes theoretical. That is the entire justification for the grading capacitor.

What the Grading Capacitor Actually Does

A grading capacitor is a high-voltage capacitor connected permanently in parallel with each interrupting gap. It performs two jobs, and buyers usually only know about the first.

It forces the voltage to divide evenly. Because the grading capacitance is an order of magnitude larger than the stray capacitance to earth, the parallel combination is dominated by the capacitor, and every break ends up with roughly the same share. The larger the capacitor relative to the stray capacitance, the closer the sharing comes to the ideal 1/n split.

It slows the transient recovery voltage. This is the part that is easy to miss. The rate of rise of recovery voltage across a gap is proportional to the current being interrupted divided by the capacitance across the gap. Adding capacitance therefore reduces the RRRV, which is exactly what a breaker needs when clearing a short-line fault, where the travelling-wave component of the TRV is fast and severe. A grading capacitor is thus a short-line fault capability device as much as a voltage-sharing device, and single-break breakers sometimes carry one for that reason alone — a subject covered separately in the guide to short-line fault switching.

There is a limit in the other direction. A grading capacitor is a permanent parallel path, so after the breaker opens, a small capacitive current continues to flow through it. The larger the capacitance, the larger that residual current, and the more firmly the specification requires the disconnectors on either side to be opened before the circuit is treated as isolated. Oversizing a grading capacitor also adds cost, weight on a live-tank column, and stored energy that the capacitor itself must survive.

Chart of voltage share taken by the line side break against grading capacitance for two levels of stray capacitance to earth
Seventy-eight percent on one break with no capacitor; within two percent of ideal with 300 pF. The curve is steep and then flat.

Sizing: The Ratio That Matters

The design rule is simple to state and easy to get wrong in a specification: the grading capacitance has to be large compared with the stray capacitance to earth, not merely present. With the two-break equivalent circuit, the share taken by the line-side break is

V1 / V = (Cp2 + Ce) / (Cp1 + Cp2 + Ce)

where Cp1 and Cp2 are the total capacitances across each break (grading capacitor plus the interrupter’s own gap capacitance) and Ce is the capacitance from the centre of the pole to earth. Setting the two breaks equal, the table below shows what happens as the grading capacitor grows, for two representative values of stray capacitance.

Grading capacitor per breakLine-side share, Ce = 10 pF (compact / dead tank)Line-side share, Ce = 50 pF (live tank on a column)
None (gap capacitance only, ~20 pF)60.0 %77.8 %
300 pF50.8 %53.6 %
500 pF50.5 %52.3 %
1,000 pF50.2 %51.2 %
2,000 pF50.1 %50.6 %

Two conclusions follow directly. First, the step from no capacitor to a modest one is where almost all of the benefit sits; the curve is steep and then flat. Second, an outdoor live-tank breaker needs a larger capacitor than a dead-tank or GIS unit to reach the same sharing, because its capacitance to earth is higher. Manufacturers generally land in the 300 to 1,400 pF range per break, with commercially available units spanning roughly 150 to 2,500 pF. The standard that governs the component itself is IEC 62146-1.

There is a second-order effect worth writing into the specification. Capacitors have a tolerance, typically a few percent, and the worst-case sharing happens when the capacitor on the energised side sits at the bottom of its tolerance band while the others sit at the top. A wide tolerance band quietly eats the margin the nominal calculation promised. CIGRE’s work on grading capacitor operating environments treats this explicitly, and it is the reason a ±5 percent band on a 500 pF capacitor is worth arguing about while a ±1 percent band on the same part is not.

Closing Resistors: The Other Half of the Problem

Grading capacitors solve the problem of opening. Closing has a separate one.

When a breaker energises an uncharged line, the line behaves like a capacitor being fed through the surge impedance of the conductor. The voltage wave travels to the open far end and doubles there, so the open end of the line can see close to twice the source peak. If the line still holds trapped charge from a previous opening — normal during a reclose dead time — and that charge is of opposite polarity to the source at the instant of closing, the two effects add, and the surge at the remote end can reach three times peak phase voltage. That is enough to flash over insulation that is perfectly healthy.

A closing resistor, also called a pre-insertion resistor, solves this by closing in two stages. A small auxiliary contact closes first and inserts a resistor in series with the line. The line charges through that resistance over the first several milliseconds, so the travelling wave is limited to a fraction of its unrestricted amplitude. Then the main contact closes and shorts the resistor out, and the breaker carries current through its normal path.

The resistor value is not arbitrary. It is chosen relative to the surge impedance of the line, typically within the band 0.5Z to 2Z, with Z in the 300 to 500 ohm range for EHV lines. In practice that produces the familiar numbers:

System voltageTypical closing resistorPre-insertion timeDesign surge limit
500 kV350–600 Ω (commonly 400 Ω)≥ 7 ms, typically 9–11 ms≤ 2.0 p.u.
750 kV400–600 Ω≥ 8 ms≤ 1.8 p.u.
1,000 kV~600 ΩOrder of 10 msBelow 1.8 p.u.
Converter station AC filter breakersSometimes above 1,000 ΩSet by filter dutySet by filter insulation

The insertion time is a compromise rather than an optimum. The line’s transient is essentially over within about 10 ms, so there is no benefit in holding the resistor in longer; but the resistor has a finite thermal capacity, and it also has to cover the mechanical scatter between the three poles. Nine to eleven milliseconds covers both. Resistor thermal duty is normally specified as two closings within three minutes at 1.3 times rated phase voltage, which represents closing into a close-in earth fault — the worst realistic case for the resistor element.

Timing diagram of a closing resistor sequence showing resistor contact closing first main contact closing about ten milliseconds later and the line voltage rising through the resistor
Ten milliseconds of resistance buys the whole line; the first three milliseconds do most of the charging.

What the Resistor Costs You in Hardware

A closing resistor is a stack of ceramic resistor discs, each with a metallised conductive face and an insulating coating on the side wall, mounted in a housing with its own auxiliary contact and its own timing requirement. It adds mechanical parts to a mechanism that would rather have fewer, and those parts sit in the current path only for milliseconds at a time, which makes them easy to neglect and hard to test.

That combination — high pulse energy, low duty cycle, mechanical complexity — is why closing resistors have historically been one of the less reliable subassemblies on an EHV breaker, and why the industry has spent two decades trying to design them out. The most successful route is not a better resistor but no resistor at all: point-on-wave controlled switching closes each pole at the instant the voltage across the break is near zero, which eliminates the travelling wave without any series element. That approach, and the cases where it still is not enough, is covered in the guide to controlled switching and point-on-wave closing.

The honest position for a specification is that the two techniques are not equivalent. Point-on-wave needs a reliable voltage reference, a stable mechanism and a controller that stays calibrated; it cannot help when the trapped charge on the line is unpredictable, which is the case on lines with shunt reactors or on lines that may be back-fed. A closing resistor works regardless of what the line is doing, at the cost of hardware that has to be maintained. On heavily compensated 500 kV lines, that difference has been enough to keep resistors in service.

Failure Modes and What to Check

Both components fail in ways that are invisible until they matter.

Grading capacitor. The internal element is oil-impregnated paper or film in a porcelain or epoxy housing, and its characteristic failure is partial discharge leading to a progressive short between layers. A capacitor that has lost capacitance no longer balances the breaks, so one gap silently takes more voltage; a capacitor that has gone open-circuit removes the balancing effect entirely on that break. Both conditions are found by capacitance measurement and dissipation factor testing at each major service, not by looking at the breaker. Thermal instability is the other mode: a capacitor with rising losses heats itself, and the losses rise further with temperature.

Closing resistor. The dominant failure is disc cracking from pulse energy — a resistor rated for continuous power rather than pulse energy will fail the first time it takes a real closing surge. The second is timing drift: if the auxiliary contact closes too late or the main contact closes too early, the resistor is bypassed before the line has charged, and the surge returns to its unrestricted value while every test certificate still looks correct. Resistor contact timing belongs in the same test as the breaker’s own timing test, and the two are usually measured together in a commissioning test programme.

ComponentFailure modeField symptomTest that finds it
Grading capacitorLayer short, capacitance lossUneven voltage, restrike on one gapCapacitance and tan delta measurement
Grading capacitorOpen circuit at the connectionLoss of grading on one breakCapacitance measurement per break
Grading capacitorPartial discharge, thermal instabilityRising temperature, audible dischargePD measurement, thermal imaging
Closing resistorDisc cracking from pulse energyOpen resistor, no surge limitationResistance measurement of the stack
Closing resistorAuxiliary contact timing driftNormal timing test, abnormal surgeTwo-channel timing test with R contact

Specifying Both Components

Neither component appears on the one-line diagram, and both are usually bought as part of the breaker rather than specified separately. That is exactly why the requirement should be written into the technical annex rather than left to the manufacturer’s standard configuration.

  • Rated capacitance per break, with a tolerance band, and the number of breaks per pole it is intended for.
  • Rated voltage and the lightning impulse and switching impulse withstand levels, coordinated with the interrupter so that the capacitor is never the weakest dielectric in the pole.
  • Partial discharge limit at the operating voltage, measured at the factory and stated as a number.
  • Cantilever strength, for live-tank units where the capacitor hangs off the column and carries seismic and wind load.
  • Ambient temperature range — grading capacitors are commonly available for −60 °C to +90 °C, and a cold-climate project needs that stated.
  • For closing resistors: resistance value, tolerance, insertion time with its tolerance, and the thermal duty expressed as closings at a multiple of rated phase voltage within a defined period.
  • Type test evidence for both, referenced to IEC 62146-1 for the capacitor and to the breaker’s own type test report for the resistor.

For 252 kV and 550 kV equipment the two components are often the difference between a breaker that matches its nameplate and one that only matches it on the test floor. A 252 kV pole with a 1,050 kV lightning impulse level and a 50 kA breaking rating is a case where the dielectric coordination across the breaks, not the interrupting capability, sets the practical limit, and the LW-252 1050 kV lightning impulse configuration illustrates how the withstand levels are published per pole rather than per break. Comparing that with a 252 kV 50 kA split-type unit shows how the same voltage class can be arranged differently depending on whether the design is optimised for breaking capacity or for insulation coordination.

Frequently Asked Questions

Why do EHV breakers need grading capacitors at all?

Because two or more interrupting gaps in series do not share the recovery voltage equally. The capacitance from each gap to earth biases the division, and the gap nearest the live terminal takes more than its share — in the worst analysed cases, most of it. A capacitor in parallel with each gap dominates that stray capacitance and forces an approximately equal split.

How do I know whether my breaker has grading capacitors?

On a live-tank breaker they are visible as porcelain or composite cylinders mounted alongside the interrupters. On a dead-tank or GIS breaker they are inside the enclosure and only appear on the drawings and the nameplate data. Any breaker with more than one break per pole above 245 kV should be assumed to have them until the drawings say otherwise.

What happens if a grading capacitor fails?

If it short-circuits internally, the pole effectively loses a break and the remaining gaps carry more voltage, which reduces the actual breaking capability below the nameplate value. If it goes open-circuit, that break reverts to natural, unequal sharing. In both cases the breaker may still pass a routine timing test and still trip, which is why capacitance measurement belongs in the periodic test schedule rather than in a fault-finding exercise.

Is a closing resistor still needed if the breaker has point-on-wave control?

Not always. Controlled closing removes the travelling wave by closing at the right instant, and on uncompensated lines it can replace the resistor entirely. It becomes unreliable when the voltage across the break is not predictable — lines with shunt reactors, or lines that can be back-fed from the remote end — and in those cases the resistor remains the more robust answer.

Why is the closing resistor value around 400 ohms at 500 kV?

Because it is chosen relative to the line’s surge impedance, which is roughly 300 to 500 ohms for an EHV line, and the useful band is about half to twice that value. Four hundred ohms sits close to the surge impedance of a typical 500 kV line, which is the condition under which the resistor limits the travelling wave most effectively for a given insertion time.

How long should the closing resistor stay in circuit?

Typically nine to eleven milliseconds, with a minimum around seven. The line’s transient is over within about ten milliseconds, so a longer insertion buys nothing, while the resistor’s thermal capacity and the scatter between the three poles set the practical floor. The insertion time is a timing requirement on the mechanism and must be verified, not assumed from the nameplate.

The Short Version

A multi-break EHV breaker is two problems wearing one enclosure. Opening needs the recovery voltage split evenly, and a grading capacitor of a few hundred picofarads per break does that — provided it is large compared with the stray capacitance to earth and its tolerance band is tight enough not to undo the calculation. Closing needs the energisation surge limited, and a 400 ohm resistor inserted for about ten milliseconds does that — provided its timing is verified and its pulse energy rating is real. Both components are cheap, both are invisible from the outside, and both are the reason a nameplate rating is worth what the test report behind it is worth.

If you are specifying 252 kV or 550 kV equipment and need the grading capacitance, closing resistor configuration and insulation coordination confirmed against your line data, the LW-252 4000 A split-type range and the LW36-126 40 kA range show how the same platform is configured for different duties, and our engineers can review a switching study against the breaker’s actual transient performance.