A gas analysis report lands on your desk with four numbers on it: SO2 3.4 ppm, SOF2 1.1 ppm, CF4 46 ppm, H2S not detected. Someone asks whether the breaker has to come out of service. The honest answer is that those four numbers, read together and against their own history, will answer the question — but read individually against a single threshold, they will not. SF6 decomposition products are not a pass/fail measurement. They are a fingerprint, and the fingerprint only means something when you know which gas comes from which mechanism, how the adsorber in the chamber distorts the picture, and what the trend was at the last three samples.
This guide treats decomposition products as a diagnostic instrument rather than a compliance checkbox. It covers the chemistry that produces each marker, the fault types they separate, the difference between the re-use limits in IEC 60480 and the attention values used in service, why CF4 behaves differently from SO2, and the sampling discipline that decides whether the number you are arguing about is even real. For the specification side of gas quality — purity, moisture, filling — the material sits in this guide to SF6 gas quality, purity and moisture, and the two are deliberately complementary rather than overlapping.
Why pure SF6 is a useless indicator
SF6 is remarkably stable. That stability is exactly why it is used as an insulating and arc-quenching medium in a high voltage SF6 circuit breaker: the molecule absorbs electrons, slows the discharge, and then recombines almost completely once the arc is gone. In a clean, dry chamber, more than 99% of the gas decomposed by an arc recombines within milliseconds.
The byproducts that survive are the fraction that found something else to bond with before recombination could happen. Oxygen and water vapour are the two main partners, and the trace materials present in the chamber — vaporised contact metal, PTFE nozzle material, epoxy, gasket compounds — supply the rest. The reaction chain runs roughly like this:
SF6 dissociates under the arc into SF4, SF2 and free fluorine. The fluorine attacks any hydrogen available, forming HF. SF4 hydrolyses with water to SOF2, and SOF2 further hydrolyses to SO2. Where oxygen is present, SO2F2 and SOF4 also form. Where the arc touches PTFE or epoxy, carbon enters the reaction and CF4 appears. Where the arc touches metal at high energy, metal fluorides and dust are produced alongside H2S.
Two consequences follow from that chain, and both matter more than any single threshold.
First, the byproduct mix is a record of what the arc touched, not just how big the arc was. An arc in clean gas between clean contacts leaves a different signature from an arc crawling across a contaminated insulator surface, even at the same energy.
Second, moisture is not a passive passenger. It is a reagent. A chamber that is dry will produce SOF2 and hold it; a chamber with elevated moisture will push the reaction further toward SO2 and HF. This is why a moisture reading and a decomposition reading have to be interpreted together, and why a rising SO2 in a chamber with rising dew point points at a sealing problem rather than at a contact problem.
The four markers and what each one actually indicates
Field analysers typically report SO2, H2S, CO and sometimes CF4 or HF. Each has a distinct role. Treating them as four independent health scores is the most common analytical mistake in the interpretation of SF6 decomposition products; they are four views of one event history.
| Marker | Primary source | What an increase tells you | Where it misleads |
|---|---|---|---|
| SO2 | Hydrolysis of SOF2; also formed directly in high-energy arcs | Active fault energy. The most reliable single indicator of an internal problem and the best trend variable. | Adsorbers do not remove it well, so it accumulates — a low value does not prove a quiet chamber, only a young one. |
| SOF2 | Direct reaction of SF4 with water at moderate energy | Partial discharge and low-energy sparking; presence of moisture participating in the reaction | Strongly adsorbed by activated alumina and molecular sieve. A low SOF2 may mean the filter is working, not that the discharge stopped. |
| CF4 | Arc attack on PTFE nozzles, epoxy and other carbon-bearing materials | Cumulative ablation of solid insulation. A lifetime integrator of how much material the arc has eaten. | Poorly correlated with individual arc energy, because whether the arc touches polymer is partly random. Do not use it to date a single event. |
| H2S | Reaction with sulfur-bearing contaminants, metal sulfides, or arcing on contaminated surfaces | Contamination or moisture involvement rather than clean-metal arcing. A serious signal when it appears at all. | Not stably detectable at low levels in many breaker chambers; a zero reading is weak evidence of absence. |
One further marker deserves a mention even though most portable analysers cannot measure it: HF. It is the most corrosive product in the mix and the one that attacks epoxy insulators and silver-plated contact surfaces. Its presence at anything above trace level is a materials-damage indicator, not just a gas-quality indicator. Where a lab analysis is available, ask for it.
Reading the ratio rather than the level
The diagnostic value in SF6 decomposition products comes from the shape of the mix. A few patterns recur often enough to be worth memorising.
SOF2 dominant, SO2 low, H2S absent. This is the low-energy signature. Corona or partial discharge on an insulator surface, or sparking at a poor contact, generates SOF2 without the energy needed to drive it on to SO2. The absolute numbers are usually small — single-digit ppm — and the correct response is to shorten the sampling interval and look for the discharge with UHF or acoustic methods rather than to schedule an outage immediately.
SO2 dominant, SOF2 low, HF present. This is the high-energy signature. Sustained arcing or a hot spot has driven the reaction to completion, and the fluorine has found hydrogen. In a breaker that has just cleared a heavy fault, this pattern is expected and normal; the question is whether it decays. In a breaker that has not operated, it is a fault.
SO2 and H2S together, moisture elevated. Contamination and moisture are involved. The arc is running across a surface that should not be conducting, and the byproducts include sulfur compounds from that surface. This pattern is the one most often associated with a chamber that has been sitting at high humidity with a marginal seal.
CF4 high and rising, everything else modest. The interrupter has done a lot of work. Nozzle and contact ablation has accumulated. This is not a fault, it is an age, and it feeds directly into the electrical endurance assessment covered in this guide to circuit breaker endurance classes.
The numbers: re-use limits versus service attention values
Two different standards families get quoted in the same conversation, and they answer different questions. Confusing them produces both false alarms and missed faults.
IEC 60480 defines the specification for re-use of recovered SF6 — that is, whether gas taken out of a chamber is clean enough to put back into equipment. It is a gas-handling limit, not a health limit for the asset. The 2019 edition sets SF6 content above 97% by volume, air and/or CF4 below 30 000 µl/l (3% by volume), water below 200 µl/l, mineral oil below 10 mg/kg, and total acidity below 50 µl/l — with an alternative acceptance route of 12 µl/l for the sum of SO2 and SOF2, or 25 µl/l for HF.
Read that carefully. A chamber can be at 12 ppm SO2 and still pass the re-use specification, because 12 ppm of acid in a cylinder of recovered gas is a handling question. The same 12 ppm inside an operating breaker is a strong indication of an active fault. The standard is not being lenient; it is answering a different question.
| Parameter | IEC 60480 re-use limit | Typical service attention value | What the gap means |
|---|---|---|---|
| SO2 | 12 µl/l (as SO2 + SOF2) | Investigate above 1–2 µl/l; act above 5 µl/l | The service value is roughly a tenth of the re-use value because the gas is still in the asset |
| H2S | Not separately limited | Investigate above 0.5 µl/l; act above 3 µl/l | H2S is treated as a contamination flag, not an acidity budget item |
| HF | 25 µl/l | Any stable reading above trace is significant | Corrosion damage begins long before the handling limit is reached |
| CF4 | Counted within the 3% air + CF4 budget | Track the trend; no fixed action value | CF4 is a lifetime indicator, so a level without a history is uninterpretable |
| Water | 200 µl/l | 150 µl/l at commissioning; 300 µl/l in service for interrupter chambers | Moisture drives the SO2 and HF formation chain, so it belongs in the same decision |
The service column above is indicative. National practices differ, and a utility standard or the manufacturer’s instruction book always takes precedence over a generic table. What does not differ is the logic: the service thresholds are set an order of magnitude below the handling thresholds, because the consequence of being wrong is different.

Why the trend beats the threshold
Every argument in the previous section assumes a single sample. In practice a single sample is the weakest form of the evidence, for three reasons.
The first is background. A breaker that has cleared twenty faults over fifteen years will carry a nonzero SO2 reading that has nothing to do with a present problem. Without a baseline, you cannot tell that from a fault that started last month.
The second is the adsorber. Most interrupter chambers contain activated alumina or a molecular sieve whose job is to mop up moisture and the more reactive byproducts. Adsorbers are effective against SOF2 and SOF4 and much less effective against SO2 and CF4. This asymmetry distorts the fingerprint in a predictable direction: a filtered chamber reads low in SOF2 relative to SO2. If you interpret the mix without knowing the adsorber state and its last replacement date, you will misjudge the fault energy.
The third is that the interesting question is rarely “is there decomposition” but “is it still being produced”. Two samples a month apart answer that; one sample does not.
The practical rule is to plot SO2 against cumulative interrupted fault current, not against calendar time. A breaker that has not operated should show a flat line. A breaker that has operated should show a step. A step with no corresponding operation is the signal you are looking for, and it is invisible on a single-sample basis.

A worked example: what one 40 kA interruption actually does
Take a 126 kV outdoor breaker rated 40 kA short-time withstand for 3 s, of the type represented by the LW36-126 with 40 kA / 3 s short-time withstand. A close-open duty clearing a 40 kA fault in three cycles means roughly 50 ms of arcing at an arc voltage in the several-hundred-volt range. Multiplying gives an arc energy of the order of one megajoule for that single operation.
One megajoule is enough to decompose a few grams of SF6 and to ablate a measurable amount of PTFE from the nozzle throat. It is also enough to raise the SO2 concentration in a chamber of a few hundred litres by a few ppm — a step that is small in absolute terms and unmistakable on a trend plot. That is the whole reason trend analysis works: the per-event signal is tiny, and the accumulated signal is not.
This is also where the electrical endurance question connects. A breaker with a rated short-circuit breaking capacity and a defined number of rated short-circuit breaking operations has a budget for exactly this ablation. The cumulative arc energy, the accumulated CF4, and the contact erosion measured by resistance testing are three ways of measuring the same consumed budget. The materials side of that story — what the contacts are made of, how much they erode per operation, and when they are due for replacement — is covered in this guide to arcing contact materials CuW and CuCr.
What decomposition products cannot tell you
The method has a hard boundary, and it is worth stating plainly because it is the source of most misapplied gas analysis.
Gas analysis detects faults that involve the gas or the surfaces in contact with it: internal arcing, partial discharge, overheating of a conductor or contact inside the chamber, contamination on an insulator surface, and moisture ingress. It does not detect mechanical faults. A breaker with a worn latch, a fatigued disc spring, a leaking hydraulic seal or a sticking valve can be mechanically at the end of its life with a perfectly clean gas sample. The mechanical side needs its own instruments — timing, travel, and the coil current signature covered in the companion article on coil current signature analysis.
Gas analysis also cannot localise a fault within a multi-chamber breaker. Each chamber has to be sampled separately, and in a dead tank or a GIS bay that means planning sample points at the design stage rather than discovering at the first alarm that the only valve is on the common filling port.
Finally, gas analysis cannot distinguish a fault that is progressing from one that has stopped. A partial discharge that carbonised a surface and then extinguished leaves the same gas as one that is still running. Only repeat sampling separates the two, which is why the correct response to an unexpected reading is almost never an immediate outage — it is a second sample in two weeks.
Sampling discipline: how to avoid arguing about a number that is wrong
More false alarms come from sampling technique than from faulty analysers. Four rules cover most of it.
Purge the sampling line. Three to five minutes of gas flow through the hose before the analyser sees the sample is the minimum, and longer on a cold day. A line that has been sitting with air in it will read low on decomposition products and high on air content, which is a confusing combination.
Use the right materials. Stainless steel or PTFE for the sample path; avoid plastic tubing, which absorbs moisture and reacts with the more aggressive byproducts. This matters most for HF, which will not survive a long plastic line at all.
Record the conditions with the result. Pressure, temperature, and the ambient humidity at the time of sampling all affect the reading and all get lost if the technician writes only the ppm value on the sheet.
Send a cylinder sample for anything that matters. On-site electrochemical analysers are good at SO2 and adequate at H2S; they are poor at HF and cannot resolve CF4 reliably. Where a fault is suspected, a laboratory analysis by GC or FTIR gives the full spectrum and settles the question. The handling procedures that go with taking that sample safely are in this guide to SF6 gas handling on site.
| Sampling interval | Applies to | What to record |
|---|---|---|
| At commissioning | Every new chamber | Full spectrum, moisture, purity — this is the baseline that everything later is compared against |
| Annually | Breakers in normal service | SO2, moisture, density trend; CF4 if the analyser supports it |
| After every fault clearance above 60% of rating | All breakers | SO2 step size against the operation log; CF4 if available |
| Two weeks after any unexpected reading | Suspect chambers | Repeat SO2 and moisture on the same analyser, same conditions |
| After adsorber replacement | Chambers with filters | Post-filter baseline — without it, the next SOF2 reading is uninterpretable |
Turning the reading into an action
The output of a gas analysis should be a decision, not a number on a report. The decision tree is short.
SO2 below 1 µl/l and stable. No action beyond the normal interval. Keep the record.
SO2 between 1 and 5 µl/l with a flat trend. Halve the sampling interval, check the operation log for a fault clearance that explains it, and check moisture. If both are stable, this is a history, not a fault.
SO2 above 5 µl/l, or any reading that rose between two samples with no operation to explain it. This is an active internal fault until proven otherwise. Repeat the sample in two weeks, run a partial discharge survey, and plan an outage. Do not top up the gas and call it handled — topping up dilutes the reading and destroys the trend.
H2S present at all. Treat as contamination until proven otherwise: check moisture, check for a sealing problem, and inspect the chamber at the next opportunity. H2S in a clean, dry chamber should not be there.
CF4 high with everything else quiet. Not a fault. Feed it into the endurance assessment and the spares plan.
The one action that is almost always wrong is immediate de-energisation on a single unexpected reading. The one that is always wrong is a gas top-up that resets the measurement without addressing the cause. Between those two, there is a two-week repeat sample that costs an hour and resolves most cases.
If you are specifying a new bay, the design decisions that make this analysis possible later are worth raising at the enquiry stage: separate sample points per chamber, a documented adsorber replacement interval, and a gas density monitor whose alarm and lockout contacts are wired to a circuit that records events. The monitoring side is covered in this guide to the SF6 gas density monitor, and the reporting obligations that increasingly sit alongside it in this guide to SF6 emissions and F-gas regulation.
Frequently asked questions
What level of SO2 in SF6 is considered a problem?
In service, SO2 above roughly 1 to 2 µl/l warrants investigation and above 5 µl/l warrants action, depending on the utility standard. For comparison, IEC 60480 allows up to 12 µl/l of SO2 plus SOF2 in gas being recovered for re-use — a much looser limit, because that standard governs gas handling rather than asset health. The trend between samples matters more than any single value.
Does CF4 indicate arc energy or equipment age?
Equipment age and cumulative ablation, more than individual arc energy. CF4 forms when the arc attacks carbon-bearing materials such as PTFE nozzles and epoxy, and whether that happens in any given operation is partly random. Measured over many operations it accumulates monotonically, which makes it a good lifetime indicator and a poor event marker.
Why does SOF2 sometimes read lower than expected after a fault?
Because activated alumina and molecular sieve adsorbers remove SOF2 and SOF4 efficiently while leaving SO2 largely untouched. A chamber with a healthy adsorber will show a mix biased toward SO2. Without knowing the adsorber’s state and replacement date, the SOF2 reading cannot be interpreted as a fault energy indicator.
Can decomposition products detect a mechanical fault in a breaker?
No. Gas analysis detects faults involving the gas or the surfaces it touches — arcing, partial discharge, overheating, contamination. A worn latch, a fatigued spring or a leaking hydraulic seal can develop with a perfectly clean gas sample. Mechanical condition needs timing, travel and coil current signature testing.
How often should SF6 gas be sampled for decomposition products?
At commissioning to establish a baseline, annually in normal service, after any fault clearance above about 60% of rated breaking current, and two weeks after any unexpected reading. Chambers with adsorbers also need a baseline immediately after filter replacement.
Is a gas top-up an acceptable response to a rising SO2 reading?
No. Topping up dilutes the concentration and destroys the only evidence you have, while leaving the cause in place. Record the reading, find the leak or the fault, and re-sample after the repair rather than before it.
If you have a gas analysis report you cannot make sense of, or you are specifying chambers and want the sample points and monitoring scheme reviewed before the enquiry is issued, the SF6 circuit breaker technical library collects the related material and you can send the report for a second opinion.