Product Overview
This page covers a 40.5 kV gas-insulated switchgear cabinet with C, F, and V module data. The electrical table identifies different load-switch, combination-apparatus, and vacuum-circuit-breaker duties. The previous copy and table named different insulating gases, so the gas type and operating pressure are not presented as confirmed product facts and must be verified for the selected configuration.
Listed Electrical Data
| Module options | C module / F module / V module |
| Rated voltage | 40.5 kV |
| Power-frequency withstand voltage | 95 / 118 kV |
| Lightning impulse withstand voltage | 185 / 215 kV |
| Rated current | C/V module: 1250 A; F module: 125 A* |
| Short-circuit breaking current | C module: 31.5 kA; F module: 31.5 kA*; V module: 20 kA |
| Short-circuit making current | C module: 80 kA; F module: 80 kA*; V module: 20 kA |
| Short-circuit duration | 4 s |
| Mechanical life | C/F module: 5000 operations; V module: 10000 operations |
| Annual leakage rate | 0.1% |
| Protection class | IP67 / IP4X, gas chamber / housing |
*The source table marks the F-module values with an asterisk but does not provide the corresponding note. Confirm those values and their conditions before selection.
Selection Guidance
Confirm the required module, rated current, fault duty, insulation level, insulating-gas type, gas pressure, busbar arrangement, cable interfaces, operating mechanism, control voltage, protection and interlocking scheme, indoor or outdoor enclosure, applicable standard, and site conditions.
Frequently Asked Questions
Is the insulating gas confirmed as nitrogen or SF6?
No. The previous page copy and technical table conflicted, so the gas type and pressure must be confirmed from the selected configuration datasheet.
What rated voltage is listed?
The listed rated voltage is 40.5 kV.
Which module types are shown?
The source table shows C, F, and V modules for different switching duties.
What protection class is listed?
The source table lists IP67 for the gas chamber and IP4X for the housing.
What should be provided for a quotation?
Provide the single-line diagram, module arrangement, rated current, fault duty, insulation requirements, gas specification, control voltage, cable details, protection scheme, applicable standard, quantity, and destination.
Request a Quote
Send the switchgear configuration and project requirements so the electrical ratings and insulating-gas specification can be confirmed before quotation.
FAQ
Is the insulating gas confirmed as nitrogen or SF6?
No. The previous page copy and technical table conflicted, so the gas type and pressure must be confirmed from the selected configuration datasheet.
What rated voltage is listed?
The listed rated voltage is 40.5 kV.
Which module types are shown?
The source table shows C, F, and V modules for different switching duties.
What protection class is listed?
The source table lists IP67 for the gas chamber and IP4X for the housing.
What should be provided for a quotation?
Provide the single-line diagram, module arrangement, rated current, fault duty, insulation requirements, gas specification, control voltage, cable details, protection scheme, applicable standard, quantity, and destination.